LED

WHAT HAPPENED

POSSIBLE REASON

WHAT TO DO

Image RemovedImage Added

ULL – User load limit exceeded

  • The load limit has been set too low in relation to AEG configuration

  • Other possible reasons are the same as in the case of OCP or SCP

  • Modify the adjustable smart fuse settings

  • Follow the OCP or SCP guidelines

  • Contact us at support@gatee.eu

Image RemovedImage Added

OCP – Blu-Link has detected excessive current activating overcurrent protection

  • Motor damaged

  • Motor or gearbox jammed

  • Motor connection short circuit

  • Replace motor

  • Unjam motor or gearbox

  • Check and fix motor wire insulation

Image RemovedImage Added

SCP – Blu-Link has detected a current over 270 A activating short circuit protection

  • Motor damaged

  • Motor or gearbox jammed

  • Motor connection short circuit

  • Replace motor

  • Unjam motor or gearbox

  • Check and fix motor wire insulation

Image RemovedImage Added

OTP – Blu-Link temperature is too high activating over temperature protection

  • Excessively high outside temperature in combination with a tuned replica

  • Frequent short circuits and Blu-Link electrical overloads

Wait until Blu-Link temperature drops

Image RemovedImage Added

UVP1 – Battery protection was activated

Battery discharged

Charge battery

Image RemovedImage Added

UVP2 – The voltage dropped below critical level for Blu-Link to work properly

  • Battery discharged

  • The battery is worn out and has excessively high internal resistance

  • Inadequate battery type for current AEG configuration

  • Too much electrical resistance between Blu-Link and the battery

  • Motor too powerful for the battery connected

  • Motor connection short circuit

  • Jammed motor

  • Damaged motor

  • Charge battery

  • Replace battery

  • Use battery of greater capacity or voltage

  • Do not use any adaptors

  • Use standard or high-torque motors instead of high-speed ones

  • Check and fix motor wire insulation

  • Unjam motor

  • Replace motor

 

Image RemovedImage Added

UVP3 – Protection against battery overdischarge activated immediately after battery was connected

  • The number of cells differs from the number set in GCS

  • Battery discharged

  • Set the same number of cells in GCS as in battery

  • Charge battery

...