LED | WHAT HAPPENED | POSSIBLE REASON | WHAT TO DO |
---|
Image Added | OVL - The load limit was exceeded. | Too high load
| Contact us at support@gatee.eu
|
Image Added | OCP - Blu-Link detected too high current. Overcurrent protection was activated. | Too low current is set in smart fuse settings Motor is damaged Motor or gearbox is jammed Motor connections' short circuit
| Adjust smart fuse settings Replace the motor Unjam the motor or gearbox Check and fix the motor wires' insulation
|
Image Added | SCP - Blu-Link detected current over >270 A. Short circuit protection was activated. | Motor is damaged Motor or gearbox is jammed Motor connections' short circuit
| Replace the motor Unjam the motor or gearbox Check and fix the motor wires' insulation
|
Image Added | OTP - Blu-Link temperature is too high. Over temperature protection was activated. | OTP Outside temperature is too high in correlation with the demanding AEG Frequent short circuits and Blu-Link’s electrical overloads
| Wait until the temperature drops. |
 | UVP1 - Battery protection was activated. | The battery is discharged | Charge the battery |
 | UVP2 - The voltage dropped below 1.5 V which is critical for Blu-Link to work properly. | 1. The battery is discharged 2. The battery is worn out and has too high internal resistance 3. Inadequate battery type for given AEG configuration 4. Too much electrical resistance between Blu-Link and the battery 5. Motor too strong for the connected battery 6. Motor connections' short circuit 7. Motor is jammed 8. Motor is damaged | Charge the battery Replace the battery Use a battery with more capacity or more voltage Do not use any adapters Use standard or high-torque motors instead of high-speed ones Check and fix the motor wires insulation Unjam the motor Replace the motor
|
 | UVP3 - Protection against over-discharge of the battery. Battery protection was activated immediately after connecting the battery. | Number of cells is different than their number set in GCS The battery is discharged
| Set the same number of cells in GCS as in the battery Charge the battery
|
Image Removed | OVL - The load limit was exceeded. | Too high load
| Contact us at support@gatee.eu
|
Image Removed | OCP - Blu-Link detected too high current. Overcurrent protection was activated. | Too low current is set in smart fuse settings Motor is damaged Motor or gearbox is jammed Motor connections' short circuit
| Adjust smart fuse settings Replace the motor Unjam the motor or gearbox Check and fix the motor wires' insulation
|
Image Removed | SCP - Blu-Link detected current over >270 A. Short circuit protection was activated. | Motor is damaged Motor or gearbox is jammed Motor connections' short circuit
| Replace the motor Unjam the motor or gearbox Check and fix the motor wires' insulation
|
Image Removed | OTP - Blu-Link temperature is too high. Over temperature protection was activated. | OTP Outside temperature is too high in correlation with the demanding AEG Frequent short circuits and Blu-Link’s electrical overloads Wait until the temperature drops.
|