Congratulations on your Blu-Link!
...
Notice
You can use Blu-Link without ETU. It will work as a smart fuse and power analyzer enabling to, e.g., read telemetry data.
...
How to read DTC explanations
grafika - flaga w kolorze i z liczba plus strzałki wyjaśniające
dodać za liczbą mignięć znak “x” np. 2x
przemyśleć bardziej obrazowe oznaczanie liczby mignięć, np. warfet, 4 błyśnięcia:
Notice
If you use an ETU connected to Blu-Link, check also the ETU's DTC. The Blu-Link is designed to withstand higher power load and lower voltage than ETU, so in most cases, an ETU protection turns on earlier and the Blu-Link does not detect the problem.
LED | WHAT HAPPENED | POSSIBLE REASON | WHAT TO DO |
---|---|---|---|
OVL – The load limit was exceeded. |
|
| |
OCP – Blu-Link detected too high current. Overcurrent protection was activated. |
|
| |
SCP – Blu-Link detected current over 270 A. Short circuit protection was activated. |
|
| |
OTP – Blu-Link temperature is too high. Over temperature protection was activated. |
| Wait until the temperature drops | |
UVP1 – Battery protection was activated. | The battery is discharged | Charge the battery | |
UVP2 – The voltage dropped below 1.5 V, which is critical for Blu-Link to work properly. | 1. The battery is discharged 2. The battery is worn out and has too high internal resistance 3. Inadequate battery type for given AEG configuration 4. Too much electrical resistance between Blu-Link and the battery 5. Motor too strong for the connected battery 6. Motor connections' short circuit 7. Motor is jammed 8. Motor is damaged |
| |
| UVP3 – Protection against over-discharge of the battery. Battery protection was activated immediately after connecting the battery. |
|
|
...